Fire resistance of linear joint seals depending on the joint width and the type of mineral wool used


openaccess, Vol. 623 (7) 2024 / poniedziałek, 29 lipca, 2024

Odporność ogniowa uszczelnień złączy liniowych w zależności od szerokości zabezpieczanego złącza oraz rodzaju zastosowanej wełny mineralnej

(Open Access)

DOI: 10.15199/33.2024.07.12

Bajorek G., Górak P., Łagosz A. Fire resistance of linear joint seals depending on the joint width and the type of mineral wool used. Materiały Budowlane. 2024. Volume 623. Issue 7. Pages 90-95. DOI: 10.15199/33.2024.07.12

This paper presents the results of fire tests determining the effect of joint width and type of mineral wool used on the fire resistance of linear joint seals. Ten test pieces made with five differentmineral wools, used in 50 and 100mmwide joints, were tested. The test results showed that higher fire resistance classes were achieved for linear joint seals protected with rock mineral wool. Fire insulation increased with increasing density of the mineral wool used. In the case of fire integrity, no such pattern was confirmed. In addition, it was shown that the fire resistance of the joint decreases with increasing joint width.

W artykule przedstawiono wyniki badań ogniowych, określające wpływ szerokości szczeliny oraz rodzaju zastosowanej wełny mineralnej na odporność ogniową uszczelnień złączy liniowych. Badaniu poddano 10 elementów próbnych wykonanych przy użyciu pięciu różnych wełen mineralnych, zastosowanych w szczelinach o szerokości 50 oraz 100 mm. Uzyskane rezultaty badań wykazały, że wyższe klasy odporności ogniowej zostały osiągnięte w przypadku uszczelnień złączy liniowych zabezpieczonych skalną wełną mineralną. Izolacyjność ogniowa zwiększała się wraz ze zwiększeniem gęstości zastosowanej wełnymineralnej. W przypadku szczelności ogniowej nie potwierdzono takiej prawidłowości. Dodatkowo wykazano, że odporność ogniowa złącza maleje wraz ze zwiększaniem jego szerokości.
fire resistance; fire insulation; fire integrity; linear joints; mineral wool.

odporność ogniowa; izolacyjność ogniowa; szczelność ogniowa; złącza liniowe; wełna mineralna.
  1. Prusakov VA, Gravit MV, Simonenko YB. Superthin. Basalt Fiber as the Base of aMatrix of theFire-ResistantFilling of Deformation Joints inBuilding Structures. Glass Phys Chem. 2023; https://doi. org/10.1134/S1087659622600879.
  2. Huang Z, Jiawei Z, Zimao P, Hongbo H, Huiping A, Xulong Y, Tianxiang X. Simulation of Thermomechanical Coupling and Evaluation of the Fire Resistance for the Joints of Fabricated Frame Tunnel. Fire. 2023; https://doi. org/10.3390/fire6010003.
  3. Sędłak B, Kinowski J, Roszkowski P, Sulik P. Uszczelnienia złączy liniowych z mechanicznie wywołanym przemieszczeniem powierzchni czołowych złącza. Materiały Budowlane. 2017; 7: 20 – 23.
  4. Andres B, Livkiss K, Hidalgo JP, Van Hees P, Bisby L, Johansson N, Bhargava A. Response of stone wool–insulated building barriers under severe heating exposures. J Fire Sci. 20178; 36 (4): 315–341.
  5. Paudel D, Rinta-Paavola A, Mattila HP, Hostikka S. Multiphysics Modelling of Stone Wool Fire Resistance, Fire Technology. 2020; https://doi. org/10.1007/s10694-020-01050-5.
  6. Frangi A, Schleifer V, Hugi E. A New Fire Resistant Light Mineral Wool. Fire Technology. 2012; https://doi. org/10.1007/s10694-010-0209-2.
  7. Nagy N. Determination Of Thermal Properties Of Mineral Wool Insulation Materials For Use In Full-Scale Fire Modelling. UW Space. 2020; http://hdl.handle.net/10012/15705
  8. Fejfer Ł, Sulik P. Wymagania dotyczące bezpieczeństwa pożarowego przejść instalacyjnych, Materiały Budowlane. 2018; 6: 53 – 55.
  9. Ye Z, Abu AK, Fleischmann CM, Dhakal RP. Chapter: Modelling the thermal response of firestop sealant exposed to standard fire; Book: Life- -Cycle of Structures and Infrastructure Systems; CRC Press. 2023; ISBN 9781003323020.
Dr. Sc. Eng. Bartłomiej Sędłak, Institute of Building Technology (ITB)
ORCID: 0000-0002-4715-6438
M. Sc. Eng. Daniel Izydorczyk, Institute of Building Technology (ITB)
ORCID: 0000-0002-2687-4297
Dr. Sc. Eng. Paweł Sulik, Institute of Building Technology (ITB)
ORCID: 0000-0001-8050-8194

Dr. Sc. Eng. Paweł Sulik, Institute of Building Technology (ITB)
ORCID: 0000-0001-8050-8194

p.sulik@itb.pl

Full paper:

DOI: 10.15199/33.2024.07.12

Article in PDF file

Received: 25.03.2024 / Wpłynął do redakcji: 25.03.2024 r.
Revised: 06.06.2024 / Otrzymano poprawiony po recenzjach: 06.06.2024 r.